Intumescent seals for use when no smoke sealing is required
Features
Tested for 30 minutes with 10mm and 15mm profile size to BS 476 part 22 & 31.1
Tested for 60 minutes with 20mm, 25mm profile size to BS 476 part 22 & 31.1
Smoke seals tested to EN1634-3. Tested for 100,000 open/close cycles
Both 10mm and 15mm seals are suitable to be used with CERTIFIRE approved FD30 SL, SAL, or unlatched timber doors of max leaf size 2040 x 926mm and a minimum thickness of 42mm